jual batteries battery aki accu kering oerlikon
Type 12CP160
Part number
Part number
Part number
76100160 ( ABS – UL 94 HB)
76200160 ( ABS – UL 94 V-0)
76300160 ( ABS-PC – UL 94 V-0)
Electrical Data
Nominal voltage 12 V
Number of cells 6
Rated capacity C10 to 1.80 Vpc at 20 ° C 160 Ah
Rated capacity C8 to 1.75 Vpc at 25 ° C 160 Ah
Current/ Power for 0.5 h back-up time 1.65 Vpc 20 ° C 198 A 2166 W
Current/ Power for 1.0 h back-up time 1.67 Vpc 20 ° C 114 A 1278 W
Current/ Power for 2.0 h back-up time 1.80 Vpc 20 ° C 62.1 A 714 W
Current/ Power for 4.0 h back-up time 1.80 Vpc 20 ° C 34.9 A 406.2 W
Current/ Power for 8.0 h back-up time 1.80 Vpc 20 ° C 19.3 A 223.8 W
Current/ Power for 10.0 h back-up time 1.80 Vpc 20 ° C 16.0 A 185.4 W
Current/ Power for 20.0 h back-up time 1.80 Vpc 20 ° C 8.8 A 99 W
Conversion to capacity at 25 ° C ( 77 ° F) 20 ° C Ah x 1, 03 ( t > 1 h)
Internal resistance ( ± 10% ) to IEC/ EN 60896-21 3.6 m
Short circuit current ( ± 10% ) to IEC/ EN 60896-21 3.3 kA
Self discharge at 20 ° C to IEC/ EN60896-21 max. 3% / month
Heat loss during . oat service at 20 ° C 0.90 W
Mechanical Data
Weight ready for use 58 kg
Height of monobloc 316 mm
Height over gas collection system GCS™ 316 mm
Height over terminal connector 316 mm
Width 125 mm
Depth 558 mm
Number of terminals 1 / 1
Dimension of connector screw hole M8
Suggested/ maximum cable cross-section 50 mm² / 70 mm² * )
Connection torque 8 Nm
Terminal insulation class according to IEC/ EN 60529 IP20
Diameter of diagnostic hole for voltage at monobloc 2.5/ 5 mm
Connector ( copper, tin-coated ) rigid and insulated 40/ 80 mm2
Complete connector and terminal connection accessories available ( as 48 V/ 60 V-Set)
Environmental Data
Shelves, cabinets and racks available upon request
Installation vertically/ horizontally
Distance for cooling and ventilation
( preset with the rigid connectors)
10 mm
Flame retardancy rating case/ cover according to
Underwriters Laboratories ( UL) USA
ABS – UL 94 HB ( std.)
ABS – UL 94 V-0 ( opt.)
ABS-PC – UL 94 V-0 ( opt.)
Flame barriers at vents installed
Gas collection system GCS™ UL V-o quality available upon request
UL . le number ® MH 26065
Service life expected at 20 ° C 15 years
* ) for UPS duties the connecting cables must be dimensioned
specially
available upon request
| Cara Pembayaran | Transfer Bank (T/T) |
| Negara Asal | Amerika Serikat |